11-25
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D   
Fault Finding 
 
Drive will not power-up  Fuse blown  Check supply details, replace with correct 
fuse. 
Check Product Code against Model No. 
  Faulty cabling  Check all connections are correct and secure. 
Check cable continuity 
Drive fuse keeps blowing  Faulty cabling or 
connections wrong 
Check for problem and rectify before 
replacing with correct fuse 
  Faulty drive  Contact Parker SSD Drives 
Cannot obtain HEALTH state  Incorrect or no supply 
available 
Check supply details 
Motor will not run at switch-on  Motor jammed  Stop the drive and clear the jam 
Motor runs and stops  Motor becomes jammed  Stop the drive and clear the jam 
Motor won’t rotate or runs in reverse  Encoder fault  Check encoder connections 
  Open circuit speed 
reference potentiometer 
Check terminal 
Table 11-1 Fault Finding