EasyManuals Logo

Parker ac890 User Manual

Parker ac890
711 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #355 background imageLoading...
Page #355 background image
11-24 Trips & Fault Finding
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Alert Message IDs
ID Message Reason
6901 Keypad 6511 Keypad
42 SYSTEM SYS
Alert displayed while changing to the system menu
on pressing the PROG key.
43
SUPER USER
TRUE
SUPR Reserved for Parker SSD Drives.
44
INCOMPATIBLE
POWER BOARD
ERR6
Power board 500v and/or underlap signals
incompatible with selected product code.
45
CALIBRATION
CHECKSUM FAIL
CAL The control board calibration data is invalid.
46
INCOMPATIBLE
PCB
PCB
Software is not compatible with this version of
control card PCB.
47
INCOMPATIBLE
POWER BOARD TYPE
TYPE Stack has been marked as a 650 or Baldor stack
48
INCOMPATIBLE
EEPROM FLAGS
FLGS
Reserved flags in stack eeprom are not zero. See
comms command ri.
49
INCOMPATIBLE
POWER BOARD CODE
CODE
Product code not compatible with this version of
software.
50 KEY INACTIVE PRE
Alert shown when the RUN key is pressed when the
Pre-charge relay is still open. This implies that the
DC Link voltage is below the under-voltage trip level.

Table of Contents

Other manuals for Parker ac890

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker ac890 and is the answer not in the manual?

Parker ac890 Specifications

General IconGeneral
BrandParker
Modelac890
CategoryDC Drives
LanguageEnglish

Related product manuals