Operating the Drive
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
90/125 F 5600 F 5600
-/150
US/Canada only
F 5600
110/150 G 6600
132/200 G 9900
160/250 G 13500
180/300 G 13500
200/300 H 14850
220/350 H 14850
250/400 H 20250
280/450 H 20250
315/500 J 19800
Simply sum the DC Link capacitance for all the drives on the common DC Link and select the appropriate
pre-charge network.
For example: a system comprising 5 x 37kW, 400V Frame E drives would have a total DC Link
capacitance of:
Total
This is less than 19,500µF and thus a 56Ω, 200W (CZ463068) resistor will be adequate.