D-15
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Parameter Descriptions
TEST DISABLE
PREF: 80.03
Default:
Range: 0 to 4
This parameter expands on the MMI to show five tests. Each test can be individually disabled by setting to TRUE.
Enumerated Value : Test
0 : STATOR RES
1 : LEAKAGE IND
2 : ENCODER DIR
3 : MAG CURRENT
4 : ROTOR TIME CONST
SPD LOOP BNDWDTH
PREF: 80.20
Default: 2.0 Hz
Range: 0.0 to 500.0 Hz
Sets the target bandwidth for the speed loop autotune. After the speed loop autotune, this will display the actual bandwidth
corresponding to the speed loop gains.
SPD MAX TORQUE
PREF: 80.23
Default: 50.0 %
Range: 0.0 to 500.0 %
Sets the maximum torque that will be used in the speed loop autotune test.
SPD MAX SPEED
PREF: 80.24
Default: 50.0 %
Range: 15.0 to 100.0 %
Sets the maximum speed that will be used in the speed loop autotune test
ACTIVE
PREF: 80.09
Default:
Range: FALSE / TRUE
This indicates the current state of the Autotune sequence. The Autotune sequence is operational when displaying TRUE.