D-143
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Feedback used to indicate that the external contactor has been closed. It must be TRUE for the sequencer to proceed from the
SWITCHED ON state to the READY STATE, refer to SEQUENCER STATE.
FALSE / TRUE
This provides a means of electronically inhibiting Drive operation. Whilst running, setting this parameter to FALSE disables
the Drive operation and causes the motor to coast.
Whilst running or jogging, setting this parameter to FALSE causes the Drive to ramp to zero. The rate is set by FAST STOP
RATE in the STOP function block. The action of setting NOT FAST STOP to TRUE is latched. The Drive cannot be restarted
until fast stop
is completed.
Setting this parameter to FALSE disables the Drive operation and causes the motor to coast. The action of setting this
parameter to TRUE is latched. The Drive can not be restarte
d until the coast stop is completed.
Detailed description of the sequencer states, as indicated by the SEQUENCER STATE parameter, is described in Appendix B.
For remote setpoints, setting this parameter TRUE inverts the demanded direction of motor rotation.
On a transition to TRUE, this input clears latched trips.
This allows the rising edge of run command to clear latched trips.
If TRUE, this allows the Drive to go directly to run mode on power-up if in remote and a run command is present. If FALSE, a
low to high transition of the run command is required.