2PREF Name Block Type Range Default ro\rw Notes
27.09 MOTOR POLES MOTOR
INDUCTION
ENUM 0 : 2 POLE
1 : 4 POLE
2 : 6 POLE
3 : 8 POLE
4 : 10 POLE
5 : 12 POLE
4 POLE rw
27.10 POWER FACTOR MOTOR
INDUCTION
REAL 0.50 to 0.99 0.86 rw 3
27.11 OVERLOAD MOTOR
INDUCTION
REAL 1.0 to 5.0 2.0 rw 3
27.14 STATOR RES MOTOR
INDUCTION
REAL 0.0000 to 250.0000 Ohm 0.2851 Ohm rw 3,5
27.15 LEAKAGE INDUC MOTOR
INDUCTION
REAL 0.00 to 300.00 mH 9.08 mH rw 3,5
27.16 MUTUAL INDUC MOTOR
INDUCTION
REAL 0.00 to 3000.00 mH 36.30 mH rw 3,5
27.17 ROTOR TIME
CONST
MOTOR
INDUCTION
REAL 10.00 to 30000.00 ms 506.08 ms rw 3,5
27.23 TOTAL INERTIA MOTOR
INDUCTION
REAL 0.0000 to 300.0000
kgm2
0.0000 kgm2 rw 5
29.01 DEFLUX TIME INJ BRAKING REAL 0.1 to 20.0 s 1.0 s rw 3,5
29.02 FREQUENCY INJ BRAKING REAL 1.0 to 500.0 Hz 6.0 Hz rw 3,5
29.03 I-LIM LEVEL INJ BRAKING REAL 50.00 to 150.00 % 100.00 % rw
29.04 DC PULSE INJ BRAKING REAL 0.0 to 100.0 s 2.0 s rw 3,5
29.05 FINAL DC PULSE INJ BRAKING REAL 0.0 to 10.0 s 3.0 s rw 3,5
29.06 DC LEVEL INJ BRAKING REAL 0.00 to 25.00 % 1.25 % rw 3,5
29.07 TIMEOUT INJ BRAKING REAL 0.0 to 600.0 s 90.0 s rw
29.08 BASE VOLTS INJ BRAKING REAL 0.00 to 115.47 % 75.00 % rw 3,5
29.09 ACTIVE INJ BRAKING BOOL 0 : FALSE
1 : TRUE
FALSE ro Output