EasyManua.ls Logo

Parker ac890 - Wire Sizes

Parker ac890
711 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications E-44
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Wire Sizes
North American wire sizes (AWG) are based on NEC/NFPA-70 for ampacities of thermoplastic-insulated
(75ºC) copper conductors assuming not more than three current-carrying conductors in raceway or cable,
based on ambient temperature of 30ºC.
The wire sizes allow for an ampacity of 125% of the rated input and output amperes for motor branch-
circuit conductors as specified in NEC/NFPA-70.
Model Number Description Power Input
Power Output
Brake
Bus Bar Connections
Wire Connections
890CS-5xxxxx
890CS-5xxxxxB
Terminal Capacity
AWG / mm
2
20 to 4 /
0.5 to 16
10mm by 3mm 20 to 4 / 0.5 to 16
20 to 6 /
0.5 to 10
Tightening Torque Nm
Sleeved
Lug
2.0 to 2.3
2.5 to 3.0
2.0
2.0
2.0 to 2.3
2.5 to 3.0
1.2
1.2
890CS-532320B
Wire size AWG / mm
2
8 / 10
10mm by 3mm
8 /10
10 / 6.0
890CS-532540B
Wire size AWG / mm
2
4 / 25
10mm by 3mm
4 / 25
10 / 6.0
890CS-5xxxxxD
Terminal Capacity
AWG / mm
2
4 to 4-0
25/ 95
10mm by 3mm
4 to 4-0
25/ 95
20 to 6 /
0.5 to 10
Tightening Torque Nm
15 to 20
2.0
15 to 20
1.2
890CS-533108D
Wire size AWG / mm
2
1-0 / 50
10mm by 3mm
2-0 / 70
3 / 25
890CS-533162D
Wire size AWG / mm
2
4-0 / 95
10mm by 3mm
4-0 / 95
1 / 50

Table of Contents

Other manuals for Parker ac890