WWAARRNNIINNGG
DURING THIS TEST, THE SAFETY FUNCTION MUST NOT BE RELIED ON BECAUSE AT TIMES ONLY
ONE CHANNEL WILL BE ACTIVATED AND THEREFORE THE INTENDED SAFETY FUNCTION MAY
NOT BE AVAILABLE. ALSO STO WILL BE ACTIVATED WHILE THE MOTOR IS ROTATING, WHICH IS
NOT THE NORMAL OPERATION. THEREFORE THE USER MUST ENSURE IT IS SAFE TO DO THIS
TEST BY USING AN APPROPRIATE RISK ASSESSMENT AND TAKING ANY ADDITIONAL RISK
REDUCTION MEASURES.
TThhee ffoolllloowwiinngg tteesstt sstteeppss mmuusstt bbee ppeerrffoorrmmeedd::
SSTTOO tteesstt
CCoommpprreehheennssiivvee CChheecckk,, AAccttiivviittyy EExxppeecctteedd rreeaaccttiioonn aanndd eeffffeecctt
1
Ensure that no harm can come to personnel or
equipment if the motor turns.
2 Apply +24V DC to terminals X11/01 and X11/03.
3 Switch on power and 24V supply voltage.
No error must be present in the drive
system. X11/05 and /06 must be OFF.
4
Configure the drive and associated equipment if necessary so that
it can be started and stopped, and a speed setpoint provided.
No error must be present in the drive
system. X11/05 and /06 must be OFF.
5
Try to start the drive with a non-zero setpoint. This
setpoint value will be referred to as SPT1 for brevity in
these tests. Leave this set throughout all tests.
Drive must start and motor must turn at
SPT1. X11/05 and /06 must be OFF.
CChhaannnneell AA CChheecckk::
SSTTOO tteesstt
CCoommpprreehheennssiivvee CChheecckk,, AAccttiivviittyy EExxppeecctteedd rreeaaccttiioonn aanndd eeffffeecctt
6
With drive running and motor turning, momentarily
disconnect terminal X11/01 (maximum duration of
disconnect = 1 second), while retaining +24V at terminal
X11/03.
Motor must immediately coast to rest.
Drive must report STO trip immediately.
X11/05 and /06 must remain OFF.
7
Ensure terminals X11/01 and X11/03 are both 24V. Try to
restart the drive.
Drive must restart at SPT1.
STO trip must clear.
X11/05 and /06 must remain OFF.
CChhaannnneell BB CChheecckk::
SSTTOO tteesstt
CCoommpprreehheennssiivvee CChheecckk,, AAccttiivviittyy EExxppeecctteedd rreeaaccttiioonn aanndd eeffffeecctt
8
With drive running and motor turning, momentarily
disconnect terminal X11/03 (maximum duration of
disconnect = 1 second), while retaining +24V at terminal
X11/01.
Motor must immediately coast to rest.
Drive must report STO trip immediately.
X11/05 and /06 must remain OFF.
9
Ensure terminals X11/01 and X11/03 are both 24V. Try to
restart the drive.
Drive must restart at SPT1.
STO trip must clear.
X11/05 and /06 must remain OFF.