Changing cycle mode
34 K-MT1-8_EN_082014
Note:
The compressor synchronisation controller is a higher-level controller
than the pressure dew point controller. When both options are in
place, the compressor synchronisation controller is treated as the
prime controller.
With dewpoint-sensing control (optional)
Dryers equipped with dewpoint-sensing control operated in variable cycle mode,
based on the measured dewpoint of the dried air at the compressed air outlet. As
soon as a certain dewpoint is reached, as the drying agent in the absorbing
chamber is saturated, the chambers are switched.
The dewpoint at which a switchover is made is preset at the factory.
How do I change cycle mode?
Wait until the dryer has reached the pressure build-up phase (phase prior to
switchover).
One LED for Adsorption B1/B2 is on in the flow diagram.
The programme continues the cycle.