Parker Hannifin S.p.A. - Divisione S.B.C. LVD User’s Manual
94
Appendix G : flash information
• TO SAVE PARAMETERS USE b99.15
• TO SAVE THE PLC PROGRAM USE b99.14
• TO CHANGE PLC INSTRUCTIONS b99.13 MUST BE SET TO 0
• WHEN CHANGING OPERATING MODE USE b99.11 TO LOAD RELATIVE
DEFAULT PARAMETERS (b40.2 MUST BE SET TO 0)
• CAUTION, BEFORE CHANGING Pr31 ENSURE b40.2=0
• SPEED REFERENCE WILL BE LIMITED TO VALUE OF Pr32
• WHEN USING TORQUE CONTROL Pr2 AND Pr3 MUST BE SET TO 1000
• TO USE THE ACTIVE OPERATING MODE b40.2 MUST BE SET TO 1
• IF USING Pr32 TO CHANGE FEEDBACK RESOLUTION ON THE FLY, TORQUE
COMPENSATION MUST BE DISABLED (b42.6=0)
• IF READ/WRITE PARAMETERS CANNOT BE CHANGED USING THE KEYPAD,
MAKE SURE THAT b99.7 IS SET TO 0; IF THIS IS THE CASE, THE PARAMETERS
IN QUESTION ARE PROBABLY CHANGED BY THE PLC PROGRAM