66 VMM1210
Test
Test Specifications
Ref #
Test Specification
Test Description
Deviation?
15.
J1455 (Jun 2006)
Section 4.13.1.1 and
Section 4.13.1.2
Operating Voltage
No
16.
EP455 (Feb 03)
Section 5.10.6
Starting Voltage
Yes
4
17.
EP455 (Feb 03)
Section 5.10.7
Operational Power Up
Yes
5
18.
J1455 (Jun 2006)
Section 4.13.1
Jumper Starts Voltage
Yes
6
19.
EP455 (Feb 03)
Section 5.10.3
Steady State Reverse Polarity
No
20.
EP455 (Feb 03)
Section 5.10.4
Short Circuit Protection
Yes
7
21.
EP455 (Feb 03)
Section 5.11.1
Transient Accessory Noise
No
22.
EP455 (Feb 03)
Section 5.11.2
Transient Alternator Field Decay
Yes
8
23.
EP455 (Feb 03)
Section 5.11.3 Level 1
Transient Batteryless Operation
No
24.
J1455 (Jun 2006)
Section 4.13.2.2.1
Transient Inductive Load Switching
Yes
9
25.
J1455 (Jun 2006)
Section 4.13.2.2.1
Transient Load Dump
Yes
10
26.
J1455 (Jun 2006)
Section 4.13.2
Transient Mutual Coupling Power
Lines
No
27.
J1455 (Jun 2006)
Section 4.13.2.2.3.2
Electrostatic Discharge Operating
Yes
11
28.
J1455 (Jun 2006)
Section 4.13.2.2.3.1
Electrostatic Discharge Handling
No
29.
J1455 (Jun 2006)
Section 4.13.3.4.2
Radiated Susceptibility
Yes
12
30.
J1455 (Jun 2006)
Section 4.13.3.4.1
Radiated Emissions
Yes
13
32.
EP455 (Feb 03)
Section 5.3 Level 1
Dust (non-operational)
No
4
Test for impaired function at 6.48V. Unit designed to operate at 6.48V.
5
Rate changed to 1 V/s instead of 1 V/ms.
6
Maximum voltage changed to 36 V instead of 48 V.
7
Applied +24V from a battery source.
8
Used Rs=10 Ohms and repetition = 45 seconds due to equipment limitation.
9
Voltage applied: 14 ±500e^ -t/.001 V, and 28 ±500e^ -t/.001 V,
10
Used Rs=1 Ohm and repetition= 90 seconds due to equipment limitation.
11
Used 330 pF capacitor through a 2 kOhms resistor (Correct parameter as per SAE J1113/13 Figure 1A).
12
Chamber size does not meet standard requirements, efield not uniform across the frequency range, due to the size of the
chamber.
13
Could not meet chamber dimensions requirements.