J1455 (Jun 2006)
Section 4.13.1.1 and
Section 4.13.1.2
EP455 (Feb 03)
Section 5.10.6
EP455 (Feb 03)
Section 5.10.7
J1455 (Jun 2006)
Section 4.13.1
EP455 (Feb 03)
Section 5.10.3
Steady State Reverse Polarity
EP455 (Feb 03)
Section 5.10.4
EP455 (Feb 03)
Section 5.11.1
Transient Accessory Noise
EP455 (Feb 03)
Section 5.11.2
Transient Alternator Field Decay
EP455 (Feb 03)
Section 5.11.3 Level 1
Transient Batteryless Operation
J1455 (Jun 2006)
Section 4.13.2.2.1
Transient Inductive Load Switching
J1455 (Jun 2006)
Section 4.13.2.2.1
J1455 (Jun 2006)
Section 4.13.2
Transient Mutual Coupling Power
Lines
J1455 (Jun 2006)
Section 4.13.2.2.3.2
Electrostatic Discharge Operating
J1455 (Jun 2006)
Section 4.13.2.2.3.1
Electrostatic Discharge Handling
J1455 (Jun 2006)
Section 4.13.3.4.2
J1455 (Jun 2006)
Section 4.13.3.4.1
EP455 (Feb 03)
Section 5.3 Level 1
Test for impaired function at 6.48V. Unit designed to operate at 6.48V.
Rate changed to 1 V/s instead of 1 V/ms.
Maximum voltage changed to 36 V instead of 48 V.
Applied +24V from a battery source.
Used Rs=10 Ohms and repetition = 45 seconds due to equipment limitation.
Voltage applied: 14 ±500e^ -t/.001 V, and 28 ±500e^ -t/.001 V,
Used Rs=1 Ohm and repetition= 90 seconds due to equipment limitation.
Used 330 pF capacitor through a 2 kOhms resistor (Correct parameter as per SAE J1113/13 Figure 1A).
Chamber size does not meet standard requirements, e–field not uniform across the frequency range, due to the size of the
chamber.
Could not meet chamber dimensions requirements.