12 - MASTER PROGRAMMING MODE
SXT continued
Figure 22
Range: Off-99 days
11. Regeneration Time
Press the Extra Cycle button. Use this display to set the
Regeneration Time. This setting species the time of day the
control will initiate a delayed, manually queued, or day override
regeneration. This option setting is identied by "RT" in the
upper left hand corner of the screen. Use the Up and Down
buttons to adjust the value as needed.
Figure 23
12. Regeneration Cycle Step Times
Press the Extra Cycle button. Use this display to set the
Regeneration Cycle Step Times. The different regeneration
cycles are listed in sequence based on the valve type selected
for the system, and are identied by an abbreviationn in the
upper left-hand corner of the screen. The abbreviations used
are listed below.
Abbreviation Cycle Step
BD Brine Draw
BF Brine Fill
BW Backwash
RR Rapid Rinse
SV Service
If the system has been congured with the "Other" valve type,
the regeneration cycles will be identied as C1, C2, ..., C20.
Cycle steps can be programmed in any order using the Up or
Down buttons with the following selections. Up to 20 individual
cycles can be set. Time for each cycle can be set from 0 to 199
minutes. Setting a cycle step time to 0 will cause the control
to skip that step during regeneration, but keeps the following
steps available. Use the Up and Down buttons to adjust the
value as needed. Press the Extra Cycle button to accept the
current setting and move to the next parameter. Program the
last cycle step as LC which forces the valve back to the service
position.
Abbreviation Cycle Step
RR Rapid Rinse
BD Brine Draw
SR Slow Rinse
BW Backwash
RF Rell
SP Service Position
LC Last Cycle
Figure 24
Range: 0-199 minutes
13. Day of Week Settings
Press the Extra Cycle button. Use this display to set the
regeneration schedule for a system congured as Day of Week
control. The different days of the week are identied as D1, D2,
D3, D4, D5, D6, and D7 in the upper left-hand corner of the
display. Set the value to "ON" to schedule a regeneration or
"OFF" to skip regeneration for each day. Use the Up and Down
buttons to adjust the setting as needed. Press the Extra Cycle
button to accept the setting and move to the next day. Note
that the control requires at least one day to be set to "ON" If all
7 days are set to "Off", the unit will return to Day 1 until one or
more days are set to "ON".
Figure 25
14. Current Day (Display Code CD)
Press the Extra Cycle button. Use this display to set the current
day on systems that have been congured as Day of Week
controls. This setting is identied by "CD" in the upper left-hand
corner of the screen. Use the Up and Down buttons to select
from Day 1 through Day 7.
Figure 26
14 • MR12 Fleck 5800 LXT & SXT Downow/Upow