EasyManua.ls Logo

Phocos Any-Grid Series - Page 11

Phocos Any-Grid Series
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.phocos.com 10 | P a g e
Any-Grid model
PSW-H-5KW-
230/48V
PSW-H-3KW-
230/24V
PSW-H-3KW-
120/24V
PSW-H-5KW-120/48V
PSW-H-6.5KW-120/48V
PSW-H-8KW-230/48V
AC input and output
cable cross-section
4 ~ 10 mm², AWG 7 ~ AWG 11 6 ~ 16 mm², AWG 4 ~ AWG 9
Circuit breaker rating
40 Aac
280 Vac
30 Aac
280 Vac
40 Aac
140 Vac
60 Aac, 280Vac for PSW-H-8KW-
230/48V, 140Vac for 120Vac models
Steps to conne ct the AC source and AC loads:
1. WARNING: Ensure the battery cable fuse is removed or breaker is secured in the open position.
WARNING: Ensure the AC source breaker is secured in the open position and there is no voltage on the
conductors before continuing.
2. Remove 10 mm / 0 .4 in of insulation for the six AC conductors (neutral“N”, live “Land protective earth“PE”
for the AC source and loads).
3. Insert t he thre e AC source wires through the rectangular casing hole (cable gland for 120 Vac models and
PSW-H-8KW-230/48V) markedACINPUT. Insert the PEprotective conductor first into the
corresponding AC input terminal and tighten with a torque of 1.4 ~ 1.6 Nm (1.0~ 1.2 lbfft). Repeatfor the
neutral“N”and live “L conductors.
PSW-H-5KW-120/48V, PSW-H-6.5KW-120/48V All other models
and PSW-H-8KW-230/48V
Fig. 7: AC input connection
4. Insert t he thre e AC load wires through the rectangularcasing hole (cable gland for120 Vac models and PSW-
H-8KW-230/48V) mar ked ACOUTPUT. Insert the“PE”protective conductor first into the corresponding
AC output terminal and tighten with a torque of 1. 4 ~ 1 .6 Nm (1.0 ~ 1.2 lbfft). Repeatfor the neutral“N”and
live “Lconductors.
PSW-H-5KW-120/48V, PSW-H-6.5KW-120/48V All other models
and PSW-H-8KW-230/48V
Fig. 8: AC Output connection
5. Make sure the six wires are securely connected.
CAUTION: Over-tightening the terminal screws can cause damage to the terminal, under-tightening
can cause a loose connection and excessive heat during operation, make sure to use the prescribed
torque. Ensure none of the conductor insulation is jammed between the terminal contacts.
CAUTION: Ensure the polarity is correct on all wires. Failure to do so may cause a short-circuit at the
AC source when several units are working in parallel operation.

Other manuals for Phocos Any-Grid Series

Related product manuals