EasyManua.ls Logo

Phoenix Contact Axioline F AXC Series - Diagnostic Parameter Register

Phoenix Contact Axioline F AXC Series
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UM EN AXL F SYS DIAG
14
PHOENIX CONTACT 8663_en_03
1.3.2 Diagnostic parameter register
The diagnostic parameter registers are always written to when a fault occurs and whenever
one of the error bits is set (F_PW_BIT, F_PF_BIT, F_BUS_BIT, F_CTRL_BIT). Otherwise,
the diagnostic parameter register has the value 0000
hex
.
The diagnostic parameter registers provide additional information on the status indicated in
the diagnostic status register when the error bits specified above are set.
The diagnostic parameter register 1 contains the error code.
An overview of the error codes can be found in Section 2, “Error codes”.
The diagnostic parameter register 2 contains additional information. For localized bus or I/O
errors, this is the error location or the device number. The error location is stored as a slot
number. This starts at 1 and corresponds to the sequential number of the Axioline F mod-
ules that are installed one after another.