OPERATING AND ASSEMBLY INSTRUCTION HEAT PUMP COMBINATION UNIT PKOM4 PAGE 10
SPECIALIST PERSONNEL GENERAL
USER
Operation of the unit is exclusively
permissible with a connected
air duct or mounted system
components such as silencers, in order to
ensure that, for example, fans or electrical
installation parts, cannot be touched with
the hand.
In the event of any errors or
defects that can cause harm to
persons or property, the system
must be put out of operation immediately.
Any further use must be actively prevented
until the unit is fully repaired.
If there are signs of apparent damage on
the unit or the corresponding installation
parts, the heat pump combi unit must be
switched o automatically and must be
disconnected from the mains. Be aware of
your safety and of hazards when opening
the unit or removing cover plates. Any work
practices that could potentially impair the
safety of the unit are prohibited.
The heat pump combi unit may be operated
only in accordance with the project doc-
umentation. which shall comply with the
Equipment and Product Safety Act and the
pertinent provisions of the EC Directives
and Standards.
Consider environmental impacts and
refrain from installing the heat pump
combi unit in the vicinity of flammable
liquids or gases, in swimming pools or in
areas exposed to chemicals or hazardous
substances.
Never operate the heat pump combi unit
without an air filter. Air filters must be
checked regularly for dirt and damage and
replaced, if necessary. The air filters must
be changed at least every six months or
when the “Change Filter” message appears
on the control unit. Use original replace-
ment filters only. If the system is not used
for an extended period, the air filters must,
for hygienic reasons, be replaced prior to
re-commissioning.
Health hazard by leaking refrig-
erant and refrigerator oil:
The unit is designed so as to
ensure that the refrigerant will never come
into contact with the drinking water, even if
there is a leakage in the cooling circuit. In
the case of leakages, however, refrigerant
may enter the atmosphere.
Gases or vapours, do not inhale.
Avoid skin and eye contact.
Directly at the leakage point,
refrigerant may cause local frost-
bite at the corresponding parts
of the body. When working on the cooling
circuit, protective gloves must be worn!