OPERATING AND INSTALLATION MANUAL HEAT PUMP COMBI UNIT PKOM4 PAGE 17
USER
GENERALSPECIALIST PERSONNEL
Setpoint
The desired hot water temperature can be
set here.
Enable
Hot water operation can be enabled, inhibit-
ed or activated via a scheduler.
Legionella protection
Legionella protection is carried out by
default every 14 days. This function can be
activated or deactivated here.
E-booster
Serves to start rapid warm-up of the tank
via the heat pump and the heating element.
After the setpoint temperature has been
reached, this function is deactivated again.
E-heating
The function of the E-heating can be gener-
ally enabled or inhibited here.
The inhibit is temporarily can-
celled for the time legionella pro-
tection is executed. The E-booster function,
however, is not provided!
Setpoint Eco
Here, the desired hot water temperature for
the eco mode (see Section 14.6.3, page 38)
can be entered.
8.1.6 Hot water temperature
Hot water
50.0 °C
Setpoint
Enabled
Legionella protec.
Yes
E-Booster Off
Yes
Hot water
Elect. Heater
Yes
65.0 °C
Setpoint Eco