OPERATING AND INSTALLATION MANUAL HEAT PUMP COMBI UNIT PKOM4 PAGE 19
USER
GENERALSPECIALIST PERSONNEL
In this submenu the following settings can
be made.
Air volumes
Level 1: Required air volume for the mini-
mum hygienic air change (absence mode).
Level 2: Required air volume in normal
ventilation mode in presence mode.
Level 3: Required increased air volume in
heat pump operation – heating.
Level 4: Required increased air volume in
heat pump operation – cooling.
If the heat pump is running in heating or
cooling mode, level 3 or 4 is
activated automatically for this
period of time. A minimum air volume
is necessary to transport a sucient
amount of heating or cooling energy.
Schedulers
Here the schedulers for the dierent areas
can be programmed.
Schedulers air volumes and temperature
1 Day on which the scheduler applies
2 Starting time of the air volume or
temperature selected
3 Second starting time of the air volume or
temperature selected
4 A third starting time can be selected
5 The scheduler of this day is accepted for all days
of the week
Scheduler hot water
During the period selected, water heat-up
by the heat pump and the E-heating is
enabled.
8.2.2
Settings
USER
GENERALSPECIALIST PERSONNEL
Settings
Schedulers
Air volumes
Additional function
Date & time
Language
Settings ventilation level
85 m³/hLevel 1
120 m³/hLevel 2
165 m³/hLevel 3
220 m³/hLevel 4
Settings scheduler
Room temperature
Air volumes
Hot water
Heating circuit (AF)
Scheduler hot water
to
00
01
from
Hot water
00
23
Scheduler air volume
from 06:00 level 3
from 08:30 level 1
Apply to all days
Monday
2
3
4
5
1
Scheduler room temperature
from 06:00 normal
from 18:30 lowered
Apply to all days
Monday
2
3
4
5
1