EasyManuals Logo

Pilot Communications SPM33 User Manual

Pilot Communications SPM33
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
40012
RO Total active power high
word
power. Calculation factor:
0.1, unit: W. If use CT,
then customers need to
multiply by CT ratio.
40013
RO Total reactive power low
word
LINT32
Secondary side reactive
power. Calculation
factor: 0.1, unit: var. If use
CT, then customers need
to multiply by CT ratio. 40014
RO Total reactive power high
word
40015
RO Total power factor INT16 Calculation factor: 0.001.
40016
RO Phase A active power
INT16 Secondary side active
power. Calculation
factor: 0.1, unit: W. If use
CT, then customers need
to multiply by CT ratio.
Only when it is 3 phase 4
wires connection mode
can the value valid.
40017
RO Phase B active power
40018
RO Phase C active power
40019
RO Phase A reactive power
INT16 Secondary side reactive
power. Calculation
44

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pilot Communications SPM33 and is the answer not in the manual?

Pilot Communications SPM33 Specifications

General IconGeneral
BrandPilot Communications
ModelSPM33
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals