RO Total active power high
word
power. Calculation factor:
0.1, unit: W. If use CT,
then customers need to
multiply by CT ratio.
40013
RO Total reactive power low
word
LINT32
Secondary side reactive
power. Calculation
factor: 0.1, unit: var. If use
CT, then customers need
to multiply by CT ratio. 40014
RO Total reactive power high
word
40015
RO Total power factor INT16 Calculation factor: 0.001.
40016
RO Phase A active power
INT16 Secondary side active
power. Calculation
factor: 0.1, unit: W. If use
CT, then customers need
to multiply by CT ratio.
Only when it is 3 phase 4
wires connection mode
can the value valid.
40017
RO Phase B active power
40018
RO Phase C active power
40019
RO Phase A reactive power
INT16 Secondary side reactive
power. Calculation
44