40020
RO Phase B reactive power
factor: 0.1, unit: W. If use
CT, then customers need
to multiply by CT ratio.
Only when it is 3 phase 4
wires connection mode
can the value valid.
40021
RO Phase C reactive power
40022 RO Phase A power factor
INT16 Calculation factor: 0.001.
Only when it is 3 phase 4
wires connection mode
can the value valid.
40023 RO Phase B power factor
40024 RO Phase C power factor
40025
RO Frequency
UNIT16 Calculation factor: 0.01,
unit: Hz
40026
RO Total active energy low
word
LUINT3
2
Calculation factor: 0.1,
unit: kWh
Range: 0-99,999,999.9
40027
Total active energy high
word
40028
RO Total reactive energy low
word
LUINT3
2
Calculation factor: 0.1,
unit: kvarh
Range: 0-99,999,999.9
40029
Total reactive energy low
word
45