40030
RO Input active energy low
word
LUINT3
2
Calculation factor: 0.1,
unit: kWh
Range: 0-99,999,999.9
40031
Input active energy high
word
40032
RO Output active energy low
word
LUINT3
2
Calculation factor: 0.1,
unit: kWh
Range: 0-99,999,999.9
40033
Output active energy high
word
40034
RO Input reactive energy low
word
LUINT3
2
Calculation factor: 0.1,
unit: kvarh
Range: 0-99,999,999.9
40035
Input reactive energy high
word
40036
RO Output reactive energy low
word
LUINT3
2
Calculation factor: 0.1,
unit: kvarh
Range: 0-99,999,999.9
40037
Output reactive energy high
word
40038 RO On-off status WORD1 D0 means 1 channel