PNOZ c1
Operating Manual PNOZ c1
22197-EN-06
| 15
Relay outputs
Utilisation category of safety contacts
AC1 at 240 V
Min. current 0,01 A
Max. current 6 A
Max. power 1500 VA
DC1 at 24 V
Min. current 0,01 A
Max. current 6 A
Max. power 150 W
Utilisation category of auxiliary contacts
AC1 at 240 V
Min. current 0,01 A
Max. current 6 A
Max. power 1500 VA
DC1 at 24 V
Min. current 0,01 A
Max. current 6 A
Max. power 150 W
Utilisation category
In accordance with the standard EN 60947-5-1
Utilisation category of safety contacts
AC15 at 230 V
Max. current 5 A
DC13 (6 cycles/min) at 24 V
Max. current 5 A
Utilisation category of auxiliary contacts
AC15 at 230 V
Max. current 5 A
DC13 (6 cycles/min) at 24 V
Max. current 5 A
Utilisation category in accordance with UL
Voltage 240 V AC G.U. (same polarity)
With current 6 A
Voltage 24 V DC G. U.
With current 6 A
External contact fuse protection, safety contacts
In accordance with the standard EN 60947-5-1
Max. melting integral 260 A²s
Blow-out fuse, slow 6 A
Blow-out fuse, gG 6 A
Circuit breaker 24V AC/DC, characteristic B/C 6 A