PNOZ s9
Operating Manual PNOZ s9
21401-EN-10
21
Relay outputs 750109 751109 751189
Number of output con-
tacts
Safety contacts (N/O),
delayed 3 3 3
Auxiliary contacts (N/
C), delayed 1 1 1
Max. short circuit current
IK
1 kA 1 kA 1 kA
Utilisation category
In accordance with the
standard EN 60947-4-1 EN 60947-4-1 EN 60947-4-1
Utilisation category of
safety contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 6 A 6 A 6 A
Max. power 1500 VA 1500 VA 1500 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 6 A 6 A 6 A
Max. power 150 W 150 W 150 W
Utilisation category of
auxiliary contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 6 A 6 A 6 A
Max. power 1500 VA 1500 VA 1500 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 6 A 6 A 6 A
Max. power 150 W 150 W 150 W
Utilisation category
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 5 A 5 A 5 A
Utilisation category of
auxiliary contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 5 A 5 A 5 A