Commissioning
OperatingManualPNOZmc7p
1003050EN02
13
6 Commissioning
6.1 Generalwiringguidelines
ThewiringisdefinedinthecircuitdiagramofthePNOZmultiConfigurator.
Pleasenote:
} Informationgiveninthe"Technicaldetails"mustbefollowed.
} Usecopperwiringwithatemperaturestabilityof75°C.
} Alwaysconnectthemountingrailtotheprotectiveearthviaanearthingterminal.This
willbeusedtodissipatehazardousvoltagesinthecaseofafault.
} Thepowersupplymustmeettheregulationsforextralowvoltageswithprotectivesep
aration.
CAUTION!
Onlyconnectanddisconnecttheexpansionmodulewhenthesupply
voltageisswitchedoff.
NOTICE
Wheninstalling,youmustrefertotheguidelinesoftheCANopenUser
Group.
6.2 Interfaceassignment
ItispossibletodefinewhichoutputsonthesafetysystemwillcommunicatewithCCLink.
TheconnectiontoCCLinkismadeviaa5pinscrewconnector.
1 2 3 4 5
DA FG/
PE
DB DG SLD
DA
FG/PE
DB
DG
SLD
1:DA(ChannelA)
2:DB(ChannelB)
3:DG(Earth)
4:SLD(Cableshield)
5:FG/PE(Functionalearth)