Automatic restart
The OSSDs automatically switch to the ON state during operation under the following con-
ditions:
} both OSSDs are wired correctly and
} no error has occurred and
} the protected field is clear and
} at least 80 ms have elapsed since the switch to the OFF state.
[1] [2] [3] [4] [5]
POWER
OSSD
2 3
4
[6]
t
1
tt
t
Interrupted
Free
Protected field
OFF
ON
ON
OFF
Fig.: Automatic start and restart timing diagram
Legend
[1] Safety light curtain is switched on
[2] Check completed successfully, OSSDs in the ON state
[3] Protected field interrupted
[4] OSSDs in the OFF state
[5] Protected field is clear again, check for errors is restarted
[6] OSSDs in the ON state
t
1
Check is begun to determine whether the protected field is clear and whether
there are errors
t
2
Response time (coded/uncoded), until OSSDs switch to the OFF state (see
Technical details [ 48])
t
3
Minimum time that the OSSDs remain in the OFF state: 80ms