EasyManua.ls Logo

Pilz PSEN opII3H Series - Checking the Safety Light Curtain

Pilz PSEN opII3H Series
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PSEN opII3H Series
Operating Manual PSEN opII3H Series
1003503-EN-05
| 36
CAUTION!
When considering the examples, please note that Pilz accepts no respons-
ibility for the specific application. In particular, they may not be used without
testing and approval.
The system manufacturer is responsible for creating appropriate safety con-
cepts for the overall plant and for connection to the programmable safety
system (including the user program). The applicable standards and regula-
tions must be considered and observed.
Checking the safety light curtain
Once the safety light grid has been installed and aligned, final inspections must be carried
out before it can be put into service.
INFORMATION
This inspection may only be carried out by qualified personnel.
Check the safety function of the safety light curtain
Procedure
In each of the indicated checks, the OSSDs must switch to the OFF state.
The OSSD status LED on the left side of the receiver must illuminate red.
1. Move the test rod slowly through the protected field (see diagram):
In the vicinity of the transmitter
In the vicinity of the receiver
In the centre of the protected field
2. Place the test rod at rest in a position in the protected field that is considered critical for
the safety assessment results

Table of Contents

Other manuals for Pilz PSEN opII3H Series

Related product manuals