PSEN opII3H Series
Operating Manual PSEN opII3H Series
1003503-EN-05
| 37
[1]
Legend
[1] Test rod
Check ambient conditions and installation
} Correct alignment and attachment
Check the seating of the mounting screws by applying pressure to the edges of the safety
light curtain. Neither the device status LED of the transmitter nor that of the receiver
may illuminate.
} Safety distance
The safety distance must comply with the requirements in Maintaining the safety dis-
tance.
} Circumventing the protected field
The danger zone must be secured so that it is impossible to access by circumventing the
protected field.
} Protected field perimeters
The protected field perimeters (see Dimensions [ 46]) must completely secure the
hazardous area, making it inaccessible.