EasyManua.ls Logo

Pilz PSS Series - Overview of PSS Systems

Pilz PSS Series
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Manual: PSS 3056 Series 2-5
• Ensure there is sufficient ventilation to prevent heat building up within the
control cabinet.
In extreme ambient conditions, additional measures may be required in
order to keep within the prescribed value range (e.g. air-conditioning
within the control cabinet).
The safety system must be installed in such a way that buttons and
switches cannot be operated unintentionally.
Connections
Cable layout must meet the EMC-guidelines stated in Chapter 3.
Each supply terminal should have its own power supply cable as shown
in the connection diagrams (do not make through-connections).
All supply terminals must be supplied with the voltages they require,
otherwise it will not be possible to carry out the module test (error
message will be generated).
The current at each slot connector should be 10 A maximum.
Screened cables are not required for digital I/Os.
• Minimum ranges for cable cross sections on field connection terminals
in mm
2
, in accordance with EN 61 131-2, 08/94:
- Digital inputs: 0.5 (AWG20) ... 1.5 (AWG16)
- Digital outputs: 0.5 (AWG20) ... 2.0 (AWG14)
- Power supply: 1.5 (AWG16) ... 2.5 (AWG12)
- Earth: 1.5 (AWG16) ... 2.5 (AWG12)
Use copper wiring.
The torque setting on the connection terminals should be 0.5 ... 0.6 Nm.
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com

Other manuals for Pilz PSS Series

Related product manuals