16 ATR171 - User manual
7.1 Selection of process value related to the command
output and to the alarms
When second input is enabled (par. 9
Sen.2
other than
di s .
) it is possible to choose
the process value to be related to command output, to alarms and to retransmission.
Following options are available:
•
Pro . 1
: Value read by input AI1;
•
Pro . 2
: Value read by input AI2;
•
Mean
: Mean between inputs AI1 and AI2;
•
di FF.
: Difference between inputs: AI1-AI2;
•
AbS. d .
: Difference between inputs AI1-AI2 as absolute value.
• Process related to command output must be set on parameter 15
c.Pro .
.
• Process related to alarms must be set on par. 34
A.1Pr.
for alarm 1, on par. 43
A. 2P r.
for alarm 2 and on par. 52
A.3P r.
for alarm 3.
• Value to retransmit must be set on par. 79
re t r.
.
It is possible to choose the visualization for display 2 on parameter 77
u.i.d.2
.
Mean and difference are available only if both inputs are configured for
temperature sensors.
7.2 Remote setpoint
It is possible to enable remote setpoint function setting
En .
on par. 16
rEM.S.
.
ATR171
FNC
PRGM
SET
PROBE
OUT
ATR171
ATR171
FNC
PRGM
SET
PROBE
OUT
RT1
3738394041
42
43
4445
29303132
33
34
3536
28
19 20 21 22 23
24
25
26 27
10 11 12 13 14
15
16
17 18
1 2 3 4 5
6
7
8 9
46474849
4...20mA
0...10V
REMOTE SETPOINT
REMOTE SETPOINT
Control Loop
Control Loop
In this configuration the value read by one of the two inputs becomes the main
control setpoint:
• If par. 15
c.Pro .
is set as
P r o .1
, AI1 becomes the main process (command) and AI2
becomes the setpoint value;
• If par. 15
c.Pro .
is set as
P r o .1
, AI2 becomes the main process (command) and AI1
becomes the setpoint value.
Remote setpoint function works only with one of these two settings of par. 15
c.Pro .
.