24 - ATR902 - User manual
29
a.1.a.t.
Alarm 1 Action Type
Denes alarm action type on operating cycle
n o . a c.
(No Action). Changes only output related to the alarm. > Default.
e. cY.s .
(End Cycle Signal). Cycle ends (STOP) with acoustic and visual
signalling. Changes output related to the alarm, buzzer sounds and
on display ashes
AL. 1
, until pressing OK.
au.si.
(Audible Signal), Only acoustic signalling: buzzer sounds.
10.2 2nd level parameters (for expert operators)
40
c. fLt.
Conversion Filter
Adc lter: number of means on analogue-digital conversions.
1…15 samplings. > Default: 10.
41
s.spu.
Starting Setpoint
Enables cycle starting setpoint to guarantee the programmed gradient for
the rst step.
di s .
(Disabled) Cycle starting setpoint disabled.
En.
(Enabled) Cycle starting setpoint selectable by the user.
En.a.t.
(Enabled Ambient Temperature) Fixed cycle starting setpoint
(25°C). > Default.
42
cHro .
Chronometer
Enables chronometer: with cycle in execution it shows the time elapsed from
cycle start; with cycle in STOP it visualizes the duration of the last cycle. At
switch-o it is reset to zero.
di s .
(Disabled) > Default
En.
(Enabled)
43
po w . c.
Power Consumption
This parameter denes the power of the heating group controlled by the device.
If the value selected is dierent from 0.0, pressing STEP (when no cycle is in
execution), it is possible to visualize the employed power consumption (Kwatt/
hour) of the last cycle. At switch-o value is lost.
0.0…999.9 KWatt/h. > Default 0.0.