22 - DRR244 - User manual
Modbus
address
Description
Read
Write
Reset
value
1013
Stato led (0=OFF, 1=ON)
Bit 0 = Led UP
Bit 6 = Led TUN
Bit 1 = Led C1 Bit 7 = Led point time 2
Bit 2 = Led C2 Bit 8 = Led MAN
Bit 3 = Led A1 Bit 9 = Led REM
Bit 4 = Led A2 Bit 10 = Led DOWN arrow
Bit 5 = Led A3 Bit 11 = Led point time 1
RO 0
1014
Key status (0=released, 1=pressed)
Bit 0 = Key UP arrow Bit 2 = Key FNC
Bit 1 = Key DOWN arrow Bit 3 = Key SET
RO 0
1015 Cold junction temperature (degrees with tenth) RO -
1016 Current CT istantaneous (Ampere with tenth) RO 0
1017 Current CT average (Ampere with tenth) RO 0
1018 Current CT ON (Ampere with tenth) RO 0
1019 Current CT OFF (Ampere with tenth) RO 0
110 0 AI1 value with decimal point selection RO -
110 6
Real setpoint (gradient) of the regulation loop 1 with decimal point
selection
RO 0
1200 Setpoint 1 of regulation loop 1 (degrees with tenth) R/W EEPROM
1201 Setpoint 2 of regulation loop 1 (degrees with tenth) R/W EEPROM
1202 Setpoint 3 of regulation loop 1 (degrees with tenth) R/W EEPROM
1203 Setpoint 4 of regulation loop 1 (degrees with tenth) R/W EEPROM
1208
Alarm 1 setpoint (degrees with tenth)
Alarm 1 upper setpoint if Par. 123
A L .1. F.
=
A.ba nd
R/W EEPROM
1209
Alarm 2 setpoint (degrees with tenth)
Alarm 2 upper setpoint if Par. 141
A L . 2. F.
=
A.ba nd
R/W EEPROM
1210
Alarm 3 setpoint (degrees with tenth)
Alarm 3 upper setpoint if Par. 159
A L . 3 . F.
=
A.ba nd
R/W EEPROM
1211
Alarm 4 setpoint (degrees with tenth)
Alarm 4 upper setpoint if Par. 177
A L .4 . F.
=
A.ba nd
R/W EEPROM
1212
Alarm 5 setpoint (degrees with tenth)
Alarm 5 upper setpoint if Par. 195
A L . 5 . F.
=
A.ba nd
R/W EEPROM
1214
Start/Stop
0=controller in STOP
1=controller in START
R/W 0
1215
Hold conversion ON/OFF
0=Hold conversion OFF
1=Hold conversion ON
R/W 0
1216
Tune management for regulation loop 1
With automatic Tune (par. 73
t u n .1 = Auto):
0=autotunig function OFF
1=autotuning ON
RO 0
With manual Tune (par. 73
t u n .1 = manu. or On cE):
0=autotunig function OFF
1=autotuning ON
R/W 0
With synchronized Tune (par. 73
t u n .1 = SYn cH.):
0=autotunig function OFF
1=command output OFF (forces the cooling)
2=command output ON (forces the heating)
3=autotuning ON
4=autotuning ended
R/W 0