User manual - DRR244 - 23
Modbus
address
Description
Read
Write
Reset
value
1218
Automatic/manual selection for regulation loop 1
0=automatic; 1=manual
R/W 0
1220
Command output percentage for regulation loop 1 (0-10000)
Heating output percentage with regulation 1 in double loop (0-10000)
R/W 0
1221
Command output percentage for regulation loop 1 (0-1000)
Heating output percentage with regulation 1 in double loop (0-1000)
R/W 0
1222
Command output percentage for regulation loop 1 (0-100)
Heating output percentage with regulation 1 in double loop (0-100)
R/W 0
1223 Cooling output percentage with regulation 1 in double loop (0-10000) RO 0
1224 Cooling output percentage with regulation 1 in double loop (0-1000) RO 0
1225 Cooling output percentage with regulation 1 in double loop (0-100) RO 0
1232
Command output manual reset for regulation loop 1: write 0 to reset the
command output.
In reading 0=reset not allowed, 1=reset allowed
R/W 0
1233
Alarms manual reset: write 0 to reset all alarms.
In reading 0=reset not allowed, 1=reset allowed
Bit0 = Alarm 1 Bit3 = Alarm 4
Bit1 = Alarm 2 Bit4 = Alarm 5
Bit2 = Alarm 3
R/W 0
1235 Alarm 1 remote stauts (0=absent, 1=present) R/W 0
1236 Alarm 2 remote stauts (0=absent, 1=present) R/W 0
1237 Alarm 3 remote stauts (0=absent, 1=present) R/W 0
1238 Alarm 4 remote stauts (0=absent, 1=present) R/W 0
1239 Alarm 5 remote stauts (0=absent, 1=present) R/W 0
1241 Value AO1 by serial (Par. 298
r t M .1 = md.bus) R/W 0
1243 Tara di zero AI1 (1=tare; 2=reset tare) R/W 0
1249 Value of remote setpoint by command 1 serial R/W 0
1251 Alarm 1 lower setpoint if Par. 123
A L .1. F.
=
A.ba nd
(degrees with tenth) R/W EEPROM
1252 Alarm 2 lower setpoint if Par. 141
A L . 2. F.
=
A.ba nd
(degrees with tenth) R/W EEPROM
1253 Alarm 3 lower setpoint if Par. 159
A L . 3 . F.
=
A.ba nd
(degrees with tenth) R/W EEPROM
1254 Alarm 4 lower setpoint if 177
A L .4 . F.
=
A.ba nd
(degrees with tenth) R/W EEPROM
1255 Alarm 5 lower setpoint if Par. 195
A L . 5 . F.
=
A.ba nd
(degrees with tenth) R/W EEPROM
1300 Setpoint 1 of regulation loop 1, with decimal point selection R/W EEPROM
1301 Setpoint 2 of regulation loop 1, with decimal point selection R/W EEPROM
1302 Setpoint 3 of regulation loop 1, with decimal point selection R/W EEPROM
1303 Setpoint 4 of regulation loop 1, with decimal point selection R/W EEPROM
1308
Alarm 1 setpoint, with decimal point selection
Alarm 1 upper setpoint if Par. 123
A L .1. F.
=
A.ba nd
R/W EEPROM
1309
Alarm 2 setpoint, with decimal point selection
Alarm 2 upper setpoint if Par. 141
A L . 2. F.
=
A.ba nd
R/W EEPROM
1310
Alarm 3 setpoint, with decimal point selection
Alarm 3 upper setpoint if Par. 159
A L . 3 . F.
=
A.ba nd
R/W EEPROM
1311
Alarm 4 setpoint, with decimal point selection
Alarm 4 upper setpoint if Par. 177
A L .4 . F.
=
A.ba nd
R/W EEPROM
1312
Alarm 5 setpoint, with decimal point selection
Alarm 5 upper setpoint if Par. 195
A L . 5 . F.
=
A.ba nd
R/W EEPROM
1351
Alarm 1 lower setpoint if Par. 123
A L .1. F.
=
A.ba nd
, with decimal point
selection
R/W EEPROM
1352
Alarm 2 lower setpoint if Par. 141
A L . 2. F.
=
A.ba nd
, with decimal point
selection
R/W EEPROM
1353
Alarm 3 lower setpoint if Par. 159
A L . 3 . F.
=
A.ba nd
, with decimal point
selection
R/W EEPROM

Table of Contents