User manual - DRR244 - 27
4
L.L.i .1
Lower Linear Input AI1
AI1 lower limit only for linear signals. Ex.: with input 4..20 mA this parameter takes value associated
to 4 mA. The value may be greater than the one entered on the next parameter.
-9999..+30000 [digit
1 p. 54
] Default: 0.
5
u .L.i .1
Upper Linear Input AI1
AI1 upper limit only for linear signals Ex: with input 4..20 mA this parameter takes value associated
to 20 mA.The value may be lower than the one entered on the previous parameter.
-9999..+30000 [digit
1 p. 54
] Default:1000
6
P. vA.1
Potentiometer Value AI1
Selects the value of the potentiometer connected on AI1
1..150 kohm. Default: 10kohm
7
i.o.L.1
Linear Input over Limits AI1
If AI1 is a linear input, allows to the process to overpass the limits (parameters 4 and 5).
diS a b.
Disabled (Default)
Enab.
Enabled
8
o . c A .1
Offset Calibration AI1
AI1 Offset calibration. Value added/subtracted to the process value (ex: usually correcting the
ambient temperature value).
-9999..+9999 [digit
1 p. 54
] (degrees.tenths for temperature sensors). Default 0.
9
G. ca .1
Gain Calibration AI1
Value multiplied to the process value to calibrate the working point. Ex: to correct the range from
0..1000°C showing 0..1010°C, set the parameter to -1.0
-100.0%...+100.0%, Default: 0.0.
10
Ltc.1
Latch-On AI1
Automatic setting of limits for AI1 linear input
diS a b.
Disabled (Default)
Stnrd
Standard
v. 0 .s t o .
Virtual Zero Stored
v. 0 . t. o n .
Virtual Zero at start
11
c.FL.1
Conversion Filter AI1
ADC Filter: Number of sensor readings to calculate mean that defines process value. NB: When
readings increase, control loop speed slows down. 1...15. (Default: 10)
12
c.Fr.1
Conversion Frequency AI1
Sampling frequency of digital / analogue converter for AI1. Increasing the conversion speed will
slow down reading stability
(example: for fast transients, as the pressure, it is advisable to increase sampling frequency).
4.17. H z
4.17 Hz (Min. conversion speed)
6.25Hz
6.25 Hz
8.33 Hz
8.33 Hz
10.0Hz
10.0 Hz
12.5 Hz
12.5 Hz
1 6 .7 H z
16.7 Hz (Default) Ideal for noises
filtering 50 / 60 Hz
19.6Hz
19.6 Hz
33.2 Hz
33.2 Hz
39.0 Hz
39.0 Hz
50.0 Hz
50.0 Hz
6 2. 0 Hz
62.0 Hz
123 Hz
123 Hz
242Hz
242 Hz
470Hz
470 Hz (Max. speed conversion)