28 - DRR244 - User manual
13
L. c.E.1
Lower Current Error 1
If AI1 is a 4-20 mA input, it determines the current value below the probe error E-05 is signaled.
2.0 MA
(Default)
2.2 M A
2.4 M A
2.6 M A
2.8 M A
3.0 M A
3.2 M A
3 .4 M A
3.6 M A
3.8 M A
14÷17 Reserved Parameters - Group A
Reserved parameters - Group A
GROUP B -
Res.
- Reserved
18÷34 Reserved Parameters - Group B
Reserved parameters - Group B
GROUP C -
cmd .1
- Outputs and regulation Process 1
35
c. o u .1
Command Output 1
Selects the command output related to the process1 and the outputs related to the alarms.
c. o2
Command on relay output Q2.
c. o1
Command on relay output Q1. (Default)
c. SSr
Command on digital output
c. vAL.
Servo-valve command with open loop on Q1 and Q2 relays
c.0-10
Command 0-10 V on analogue output AO1.
c.4 - 2 0
Command 4-20 mA on analogue output AO1.
0.10.S.R.
Command 0-10 V on analogue output AO1 with split-range function: the analogue
output sets the cooling action from 0 to 5V and heating action from 5 to 10V.
4.20.S.R.
Command 4-20 mA on analogue output AO1 with split-range function: the analogue
output sets the cooling action from 4 to 12mA and heating action from 12 to 20mA.
c.V A L.c.
Servo-valve command with open loop on Q2 and Q3 relays
Command AL. 1 AL. 2 AL. 3 AL. 4 AL. 5
c. o 2
Q2 Q1 Q3 DO1 DO2 AO1
c. o1
Q1 Q2 Q3 DO1 DO2 AO1
c. SS r
DO1 Q1 Q2 Q3 DO2 AO1
c. vA L.
Q1(open) Q2(close) Q3 DO1 DO2 AO1 -
c.0-10
(
0.10.S.R.
) AO1 (0..10 V) Q1 Q2 Q3 DO1 DO2
c.4 - 2 0
(
4.20.S.R.
) AO1 (4..20 mA) Q1 Q2 Q3 DO1 DO2
c. vA L.c.
Q2(open) Q3(close) Q1 DO1 DO2 AO1 -
NB: if an output is used for functions other than alarms (for example retransmission or command n°
2), this resource will no longer be available as an alarm and the related group will be hidden from the
parameter list. The correspondence of the functions/outputs remains however that indicated in the
tables above.
36
rEs.
Reserved
Reserved parameter
37
rEs .
Reserved
Reserved parameter
38
A c . t .1
Action type 1
Action type to control process 1.
HEAt
Heating (N.A.) (Default)
cooL
Cooling (N.C.)
39
c.HY.1
Command Hysteresis 1
Hysteresis to control process 1 in ON/OFF.
-9999..+9999 [digit
1 p. 54
] (degrees.tenths for temperature sensors). Default 0.2.