42 - DRR244 - User manual
201
A.5.L.L.
Alarm 5 Lower Limit
Lower limit selectable for the alarm 5 setpoint.
-9999..+30000 [digit
1 p. 54
] (degrees for temp. sensors). Default 0.
202
A.5. u . L.
Alarm 5 Upper Limit
Upper limit selectable for the alarm 5 setpoint.
-9999..+30000 [digit
1 p. 54
] (degrees for temp. sensors). Default 1750.
203
a .5. re.
Alarm 5 Reset
Alarm 5 contact reset type (always automatic if
A L . 5 . F.
=
c. A ux
).
A. r Es.
Automatic reset (Default)
M. r Es.
Manual reset (manual reset by keyboard or by digital input)
M.r Es.S.
Stored manual reset (keeps the output status also after a power failure)
A. r Es.t.
Automatic reset with timed activation. The alarm remains active for the time set on the
parameter 206
a.5. d e.
, even if the conditions generating it are missing. To be able to act
again, the alarm conditions must disappear.
204
A.5.S. e.
Alarm 5 State Error
Alarm 5 output status in case of error.
If the alarm output is digital (SSR):
off
Digital output OFF. Default
on
Digital ouput ON.
If the alarm output is 0-10V:
0 V
0 V. Default
10 v
10 V.
If the alarm output is 0-20 mA or 4-20 mA:
0 ma
0 mA. Default
4 ma
4 mA.
20 ma
20 mA.
21.5 m a
21.5 mA.
205
rES.
Reserved
Reserved parmeter
206
a .5. d e.
Alarm 5 Delay
Alarm 5 Delay.
-60:00..60:00 mm:ss (hh:mm if
A L . 5 . F.
=
c. a ux
). Default: 00:00.
Negative value: delay when exit alarm status.
Positive value: delay when enter alarm status
207
A.5.S. p.
Alarm 5 Setpoint Protection
Allows or not to change the alarm 5 setpoint.
FrEE
Editable by the user (Default)
Lock
Protected
Hid E
Protected and not visualized
208
A.5.Lb .
Alarm 5 Label
Selects the message displayed in case of alarm 5 intervention.
dis a b.
Disabled. (Default) 0.
lb. 01
Message 1 (see table on paragraph .)
..
lb. 20
Message 20 (see table on paragraph .)
u s e r.l.
Custom message (modifiable by the user through the App or via modbus)
209÷212 Reserved Parameters - Group K
Reserved parameters - Group K