EasyManua.ls Logo

Pixsys DRR244 - Page 43

Pixsys DRR244
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User manual - DRR244 - 43
GROUP L -
res
- Reserved
21230 Reserved Parameters - Group L
Reserved parameters - Group L
GROUP M -
d.i. 1
- Digital input 1
231
d .i .1. f.
Digital Input 1 Function
Digital input 1 functioning.
diS a b.
Disabled (Default)
2 t. s w.
2 Setpoints Switch
2 t.s w.i.
2 Setpoints Switch Impulsive
3 t.s w.i.
3 Setpoints Switch Impulsive
4 t.s w.i.
4 Setpoints Switch Impulsive
st./s t.
Start / Stop
rUn
Run
HoLd
Lock conversion (stop all conversions and display values)
tune
Performing manual tune
a u . m a .i.
Automatic / Manual Impulse (if enabled on parameter 48 or 67)
a u.m a.c.
Automatic / Manual Contact (if enabled on parameter 48 or 67)
a c t.tY.
Action Type. Cooling regulat. if D.I. is active, otherwise heating reg.
A.i. 0
Analogue Input 0. Set AI to zero
M. reS.
Manual reset. Reset the outputs if selected as manual reset.
t.1.r u n
Timer 1 run. The timer 1 count with activated D.I.
t.1. s.E.
Timer 1 Start End. D.I. starts and stops the timer 1(impulsive)
t.1.S t a.
Timer 1 Start. D.I. starts the timer 1(impulsive)
t.1. E n d
Timer 1 End. D.I. stops the timer 1(impulsive)
t.2.r u n
Timer 2 run. The timer 2 count with activated D.I.
t.2. s.E.
Timer 2 Start End. D.I. starts and stops the timer 2(impulsive)
t.2.S t a.
Timer 2 Start. D.I. starts the timer 2(impulsive)
t.2.En d
Timer 2 End. D.I. stops the timer 2(impulsive)
Lo.cfG.
Lock configuration and setpoints.
u p. k e y
Simulates the functioning of up key.
d o w n.k.
Simulates the functioning of down key.
fnc. k.
Simulates the functioning of fnd key.
s et. k.
Simulates the functioning of set key.
ext. a l.
External alarm. The controller goes on STOP and the alarms will be disabled. The
controller does not return to START automatically: for this operation, the user’s
intervention is required.
232
d.i.1.c.
Digital Input 1 Contact
Defines the resting contact of the digital input 1.
n.o pen
Normally open (Default)
n.cLos.
Normally closed
233÷238 Reserved Parameters - Group M
Reserved parameters - Group M

Table of Contents