44 - DRR244 - User manual
GROUP N -
d.i. 2
- Digital input 2
239
d .i .2. f.
Digital Input 2 Function
Digital input 2 functioning.
diS a b.
Disabled (Default)
2t. sw.
2 Setpoints Switch
2 t.s w.i.
2 Setpoints Switch Impulsive
3 t.s w.i.
3 Setpoints Switch Impulsive
4 t.s w.i.
4 Setpoints Switch Impulsive
st./s t.
Start / Stop
rUn
Run
HoLd
Lock conversion (stop all conversions and display values)
tune
Performing manual tune
a u . m a .i.
Automatic / Manual Impulse (if enabled on parameter 48 or 67)
a u.m a.c.
Automatic / Manual Contact (if enabled on parameter 48 or 67)
a c t.tY.
Action Type. Cooling regulation if D.I. is active, otherwise heating reg.
A.i. 0
Analogue Input 0. Set AI to zero
M. reS.
Manual reset. Reset the outputs if selected as manual reset.
t.1.r u n
Timer 1 run. The timer 1 count with activated D.I.
t.1. s.E.
Timer 1 Start End. D.I. starts and stops the timer 1(impulsive)
t.1.S t a.
Timer 1 Start. D.I. starts the timer 1(impulsive)
t.1. E n d
Timer 1 End. D.I. stops the timer 1(impulsive)
t.2.r u n
Timer 2 run. The timer 2 count with activated D.I.
t.2. s.E.
Timer 2 Start End. D.I. starts and stops the timer 2(impulsive)
t.2.S t a.
Timer 2 Start. D.I. starts the timer 2(impulsive)
t.2.En d
Timer 2 End. D.I. stops the timer 2(impulsive)
Lo.cfG.
Lock configuration and setpoints.
u p. k e y
Simulates the functioning of up key.
d o w n.k.
Simulates the functioning of down key.
fnc. k.
Simulates the functioning of fnc key.
set. k.
Simulates the functioning of set key.
ext. a l.
External alarm. The controller goes on STOP and the alarms will be disabled. The
controller does not return to START automatically: for this operation, the user’s
intervention is required.
240
d.i.2.c.
Digital Input 2 Contact
Defines the resting contact of the digital input 2.
n.o pen
Normally open (Default)
n.cLos.
Normally closed
241÷246 Reserved Parameters - Group N
Reserved parameters - Group N
GROUP O -
res.
- Reserved
247÷254 Reserved Parameters - Group O
Reserved parameters - Group O
GROUP P -
res.
- Reserved
255÷262 Reserved Parameters - Group P
Reserved parameters - Group P