User manual - DRR244 - 45
GROUP Q -
sft.s
- Soft-start and mini cycle
263
P r. cY.
Pre-programmed Cycle
Enables special functionings.
diS a b.
Disabled (Default)
Enab.
Enabled (all remote sepoint functions are inhibited)
264
SS.TY.
Soft-Start Type
Enables and selects the soft-start type
diS a b.
Disabled (Default)
Gra d.
Gradient
P erc.
Percentage (only with pre-programmed cycle disabled)
265
rEs.
Reserved
Reserved parameter
266
SS.G r.
Soft-Start Gradient
Rising/falling gradient for soft-start and pre-programmed cycle.
0..20000 Digit/ora (gradi.decimo/ora se temperatura). (Default: 100.0)
267
SS.Pe.
Soft-Start Percentage
Output percentage during soft-start function.
0..100%. (Default: 50%)
268
SS. tH.
Soft-Start Threshold
Threshold under which the soft-start percentage function is activated, at starting.
-9999...30000 [digit
1 p. 54
] (degrees.tenths for temp. sensors) (Default: 1000)
269
S S . ti .
Soft-Start Time
Max. Softstart duration: if the processs will not reach the threshold selected on par.
SS. tH. within
the selected time, the controller starts to regulate on setpoint.
00:00
Disabled
00:01-24:00
hh:mm (Default: 00:15)
270
M A . ti .
Maintenance Time
Maintenance time for pre-programmed cycle.
00:00-24:00
hh.mm (Default: 00:00)
271
FA. G r.
Falling Gradient
Falling gradient for pre-programmed cycle.
0
Disabled (Default)
1..10000
Digit/ora
1 p. 54
(degrees.tenths/hour if temperature)
272
de.st.
Delayed Start
To set the initial waiting time for the delayed start of the setting or cycle, even in case of a
blackout. The elapsed time is saved every 10 minutes.
0
Initial waiting time disabled: the controller starts immediately (Default)
00:01-24:00
hh.mm Initial waiting time enabled.
273÷276 Reserved Parameters - Group Q
Reserved parameters - Group Q

Table of Contents