19
463X Chlorine Systems Manual
Relay2 Rng: pH
0.00 14.0 >
Enter the range where Relay 2 will activate above and below this setpoint.
Relay2 PlsRate:
120 pulses/min >
Set the maximum pulse rate. Range: 1–400 pulses/min.
If Pulse Mode was chosen:
Find New
Sensor(s): >
Required only when a new sensor is changed while the power is on. Choose Yes or No.
Last Cal
10-18-09 >
Edit the calibration date.
End of Calibrate Menu
Relay 2 Rng: ppm
0.00 5.00 >
Enter the range where Relay 2 will activate above and below this setpoint.
Relay 2 Hys:
0.20 ppm >
This relay will be deactivated at Relay 2 Range setpoints ± this hysteresis.
Relay 2 Delay:
0.0 secs >
Set the time delay for Relay 2 to activate after reaching the setpoints set in the
Relay 2 Range.
If Window Mode was chosen:
Relay 2 Source:
pH >
Choose pH or chlorine for Relay 2.
Relay 2 Source:
pH >
Choose pH or chlorine for Relay 2.
8630 Calibrate Menu