Section V: Operation
Humidity Control
This menu contains parameters that congure the humidity control routines of the dehumidier. Water Temp Ctrl
This menu contains parameters that congure the compressor based water heating system of the dehumidier.
Water Heat First: This parameter indicates whether the control routine will use the compressor for water heating when
there is no dehumidication requirement.
Deadband: This parameter is the deadband used by the compressor based pool water heating control routine.
BAS INTERFACE
This menu contains parameters that congure the building automation system interface of the dehumidier.
MULTI-UNIT NETWORK
This menu contains parameters that congure the operation of dehumidier in a multiple unit installation.
COMPRESSOR
This menu contains parameters that congure the operation of the dehumidier compressor.
ECONOMIZER
This menu contains parameters that congure the operation of the optional eld provided and eld installed economizer
damper system.
HISTORY
The history screen provides information on the last 50 faults that have occurred in the dehumidier. It can be used for
troubleshooting by an experienced HVAC technician. The faults are recorded with a sequence number from 1 to 50.
Sequence number 1 is always the most recent fault. The following information is stored and displayed for each fault in
non-volatile memory:
Hour at which the fault occurred.
Fault Code Number
Return Air Temperature
Return Air Humidity
Discharge Pressure
Suction Pressure
Suction Temperature
Pool Water Temperature
AC Solenoid Status
Bypass Solenoid Status
Compressor Status
Reheat Solenoid Status
MANUAL MODE
The Manual Mode menu for use by qualied service personnel provides two options, Demand Control and Digital
Output Control.
UTILITIES
The Utilities menu provides sub menus for conguring units of measure and passwords for set point and service access
control.