15EGW06-PCPEG-20140813
TM
TM
Section II: Principles, Functions, and Features
TECHNICAL SUMMARY
Table 2-1. RoofPak Technical Data
DIMENSIONAL DATA
Figure 2-2. PCP RoofPak Dimensions
PCP_EG_RoofpakDimensions_20131108.eps
ROOFPAK WEIGHTS
Table 2-2. RoofPak Weights
Model Conguration Weight (lbs)
AWH/HCDH 3500/4000 With Integral Gas or Electric Heat and With Remote ACC 2,900
AWH/HCDH 3500/4000 With Integral Gas or Electric Heat and With Integral ACC 3,700
AWH/HCDH 3500/4000 With No Integral Auxiliary Heat and With Integral ACC 2,700
RoofPak weights are also included with the RoofPak Generic Product Drawings found in the Engineering Library
section of the PoolPak™ website.
Model Number AWH / HCDH 3500 - 10 Ton AWH / HCDH 4000 - 12 Ton
Pool Size (Sq. Ft.) 1,200 - 2,000 1,400 - 2,500
Reheat Capacity (MBH) 170 200
Moisture Removal (Lb/Hr@82°F/60%RH) 63 70
Pool Water Flow (GPM) 26 28
Pool Water Condenser PD (FT WC)* 20 30
Pool Water Condenser Capacity (MBH) 170 200
Outside Air (CFM)(Nominal) 0 - 2,000 0 - 2,000
Total Supply Airow CFM (Maximum) 3,500 - 7,000 4,000 - 7,000
Refrigerant Charge (lbs) 81 83
Dimensions (in inches) with integral air-cooled condenser and gas furnace
Length 264 264
Width 57.4 57.5
Height 52.5 52.2
OA
45.3
15.2
13.4
44.0
FRONT VIEW
52.5
SA
120.0 C.G.
* Side return air available; horizontal return air available without integral air-cooled condenser
LEFT VIEW
RA*
264.0