EasyManua.ls Logo

PoolPak HCD 3500 - Maintenance; Overview; Daily Maintenance; Monthly Maintenance

Default Icon
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
50 EGW06-PCPEG-20140813
TM
TM
Section V: Operation
MAINTENANCE
OVERVIEW
Periodic routine maintenance will promote extended equipment life. While PoolComPak™ units use components that
are usually maintenance free and do not require service, a simple check could result in noticing possible problems before
they develop into major problems.
DAILY MAINTENANCE
Pool water chemistry is a part of daily maintenance and it is recommended to follow National Spa and Pool Institute
standards. PoolPak™ International strongly recommends following the National Spa and Pool Institute values.
Table 5-1. Pool Water Chemistry
PoolPak™ International recommends daily logging of your pool water chemistry. MAINTENANCE AND YOUR
POOL WATER CHEMISTRY IS IMPORTANT TO PROTECT YOUR WARRANTY RIGHTS.
MONTHLY MAINTENANCE
Air Filters, inspect and replace or clean as applicable. Dirty lters restrict air ow and can cause improper unit
operation.
Ensure that the condensate collection pan is draining properly and the condensate is not overowing or being drawn
into the supply air stream. Check the condensate and overow lines to ensure that neither are clogged.
Check the operation of the blower motor and scroll. Ensure that the scroll does not rub the housing. Check for proper
belt tension. Worn or cracked belts should be replaced. Check fan and mounting brackets for tightness.
Ensure that the ALARM light is not illuminated.
ANNUAL MAINTENANCE
Inspect the refrigeration and water circuits for leaks, wear or corrosion. Corrosion on the water piping or condenser
may indicate poor pool chemical maintenance and improper chlorine and pH levels.
Check electrical components for loose wiring.
Although the exterior of the PoolComPak™ units are powder coated, wipe down unit, particularly if installed in an
area subject to dirt or chemical concentration.
Wash, brush, or vacuum the evaporator and air condenser coils. This will ensure proper heat transfer and reduce static
pressure losses. Caution should be taken not to wet electrical components inside the unit.
NOTE
If service and inspections are not performed by a competent and experienced service rm, the manufacturer
warranty may be voided.
Pool Spa
Ideal Min Max Ideal Min Max
Total Chlorine (ppm) 1.0 - 3.0 1 3 3.0 - 5.0 1 10
Free Chlorine (ppm) 1.0 - 3.0 1 3 3.0 - 5.0 1 10
Combined Chlorine (ppm) 0 0 0.3 0 0 0.3
Bromine (ppm) if applicable 2.0 - 4.0 2 4 3.0 - 5.0 2 10
pH 7.4 - 7.6 7.2 7.8 7.4 - 7.6 7.2 7.8
Total Alkalinity (ppm) 80 - 100 80 180 80 - 100 60 180
TDS (ppm) 1000 - 2000 300 3000 1000 - 2000 300 3000
Calcium Hardness (ppm) 200 - 400 150 1000 200 - 400 150 1000
Calcium Acid (ppm) 30 - 50 10 100 30 - 50 10 100

Table of Contents