VS65
POWER ELECTRONICS
24
PROGRAMMING KEYBOARD
4.3.2. Code 02 – Shutdown time
The shutdown time of 0 second means the free stopping. Excessive shutdown time maybe cause
the system is instable. (See Figure 4.3).
Figure 4.3 Stop mode
4.3.3. Code 03 – Starting delay
This is the duration from the moment while the remote startup is closed (two-wire type) until the
softstarter begins running. To use this function, the Code 09 must be set to 1. While the remote
control terminals RUN, STOP, and COM are connected and the countdown value is 0, the
softstarter will startup.
4.3.4. Code 04 – Limiting current
To use the function, Code 08 must be set to 0. The starter will begin starting with starting current
below the set value (150%~500%). When the starting is finished, the current will drop below the
rated value. If the value is larger, the allowed starting time is shorter.
Figure 4.4 Limiting current