4.3.5. Code 05 – Emergency stop setup
By setting the code 0 or 1, the user can turn on or turn off the remote emergency input. Setting 0
is disabled, setting 1 is enabled.
4.3.6. Code 06 – Interlocking delay. Code 07 – Interlocking control
The starter’s interlocking output is controlled by programming these two values. The set value of
Code 06 represents the delay time from the moment when the starter startup until the terminals is
closed. The code 07 can be assigned a control method of interlocking relay. See table on section
4.2. Code 07 must be 0 if delay.
0 1 2 3 4 5 6
START ● ● ●
RUN ● ● ● ●
STOP ● ● ●
DELAY ●
Note: Marked as “●” means “Interlock” relay is closed
4.3.7. Code 08 – Starting mode
If set to 0, it means the current mode. See 4.3.4 for starting limiting current.
If set to 1, it means the voltage mode. See 4.3.1
If set to 2, it means the heavy load mode.
4.3.8. Code 09 – Control mode
0: Only the keys RUN and STOP can be used to control startup and shutdown.
1: Remote control. Only RUN/STOP by two-wire or three-wire.
2: Keyboard + Remote control (applicable for the three-wire control method)
Both keyboard and remote control can be operated, but only the STOP-COM is closed, the “RUN”
key of keypad can be valid,
3: PC is operated by communication bus to control and monitor.
4: Keyboard + PC: Both keyboard and communication bus is valid.
5: Remote control + PC: remote RUN, STOP and communication bus is valid.