VS65
POWER ELECTRONICS
52
ANNEXE A. POWER CABINET OPERATION
8.2.1.3. Miscellaneous Tables
Real time display of sampling
Real time display of sampling
Channel 00 Measure current Ia (C7, D7) Channel 05 Protection current Ia (C9, D9)
Channel 01 Measure current Ic (C8, D8) Channel 06 Protection current Ib (C10, D10)
Channel 02 Busbar voltage Ua (C1, D1) Channel 07 Protection current Ic (C11, D11)
Channel 03 Busbar voltage Ub (C2, D2) Channel 08 Residual current Izero (C12, D12)
Channel 04 Busbar voltage Uc (C3, D3) Channel 09 Residual voltage Uzero (C4, D4)
Set value
Nº Parameter Description Setting Range
00 Setting groups Setting groups 1 – 3
01 kv1 Voltage ratio Real ratio / 10
02 ki1 Current ratio Real ratio / 10
03 Idz1 Current value of over current I 0.1 – 100A
04 tzd1 Delay time of over current I 0 – 100s
05 tqd Motor start-up time 0 – 300s
06 Idz2 Current value of over current II 0.1 -100A
07 tzd2 Delay time of over current II 0 – 100s
08 I2dz1 Current value of NPS I protection 0.1-100A
09 tzd3 Delay time of NPS I protection 0-100s
10 I2dz2 Current value of NPS II protection 0.1-100A
11 Tzd4 Delay time of NPS II protection 0-100s
12 Idz3 Current value of overload protection 0.1-100A
13 Tdz5 Delay time of overload protection 0-100s
14 10zd Current value of earth fault protection 0.1-100A
15 t10zd Delay time of earth fault protection 0-100s
16 U0dz Voltage value of residual voltage protection 3-100V
17 tu0dz Delay time of residual voltage protection 0-100s
18 Udz1 The value of under voltage protection 3-100V
19 tUudz1 Delay time of under voltage protection 0-100s
20 Udz2 The value of over voltage protection 100-140V
21 tUudz2 Delay time of over voltage protection 0-100s
22 k2 Heat factor of negative sequence current I2 0 -10
23 Tfr1 Heating time limited 0.1 – 100min
24 Cool Cooling time limited 0-5
25 GRBJ Heat factor of thermal overload protection 0-100
26 Tfd11 Delay time of temperature rise protection 0-100s
27 Tfd12 Delay time for Hi-temperature protection 0 -100min
28 Ie Rated motor current 1 – 6A