PRICE PRODIGY
®
- Manual
|
priceindustries.com
PRODIGY
®
- DIGITAL VAV DIFFUSERS
DISPLAY NAVIGATION
SETPOINT
SET LO LIMIT*
65.0°F
Day Setpoint Low Limit
· This is the lowest Setpoint allowed
· Range: 10.0°F – 100.0°F Default: 65.0°F
SET HI LIMIT*
80.0°F
Day Setpoint High Limit
· This is the lowest Setpoint allowed
· Range: 10.0°F – 100.0°F Default: 80.0°F
TEMP. UNITS
FAHRENHEIT
Temperature Units
· Fahrenheit or Celsius
· Default: °F
NITE HEAT SET*
62.0°F
Night Heat Setpoint
· Prodigy will maintain this heating setpoint when unoccupied
· Range: 10.0°F – 100.0°F Default: 62.0°F
NITE COOL SET*
83.0°F
Night Cool Setpoint
· Prodigy will maintain this cooling setpoint when unoccupied
· Range: 10.0°F – 100.0°F Default: 83.0°F
PRO. BAND*
2.0°F
Proportional Band
· Set the proportional band of the PI controller
· Default: 2.0°F
DAY DIFF.*
1.0°F
Day Differential
· Set the day differential (also known as dead band)
· Default: 1.0°F
PRESS MENU
TO EXIT
Exit
Setpoint Menu
Setpoint Limits and Temperature Units
Scroll through with Up and Down buttons, press Menu button to apply your changes *---wait---* will display as changes are applied.
*Also available over BACnet network if diffuser has BACnet option installed.