ModBus Entities
Entities listed in cyan are native to the SD230 controller are always available. Entities listed in orange are available in the TriSense configuration
when an LH200 is attached to the SD230 controller’s serial input and TriSense is enabled.
All ET230 Tags must be prefaced with Prime_RdChn[index] or Prime_WrChn[index] where index is the channel number (1-8).
Prime_RdChn[index] is used for reading the respective tags while Prime_WrChn[Index] is used to trigger a write operation to R/W tags. To read
the LeftLED of channel 3, one uses tag Prime_RdChn[3].BitGroup1,FrontPanel.0.
Discrete Coil Outputs (000001) (Read/Write)
Entity
Number
ET230 Tags
Name
Meaning
000001
BitGroup1.FrontPanel.0
LeftLED
Single/No-Tab LED
000002
BitGroup1.FrontPanel.1
RightLED
Double/Tab LED
000003
BitGroup1.FrontPanel.2
Single/No-Tab
Single/No-Tab Output
000004
BitGroup1.FrontPanel.3
Double/Tab
Double/Tab Output
000005
BitGroup1.FrontPanel.4
Fault
Fault Output
000006
BitGroup1.FrontPanel.5
TxProbeFault
Transmitter Probe Fault
000007
BitGroup1.FrontPanel.6
RxProbeFault
Receiver Probe Fault
000008
BitGroup1.FrontPanel.7
VelocityFault
Shell Velocity Fault (SD235 only)
000009
BitGroup1. HMIControls.0 &
CalValue &
CalStrobe
NetCalReq
Calibration request from HMI
000010
BitGroup1.HMIControls.1 &
ForceHighOutputsValue &
ForceHighOutputsStrobe
ForceHighOutputs
Force all outputs high from HMI
000011
BitGroup1.HMIControls.2 &
ForceLowOutputsValue &
ForceLowOutputsStrobe
ForceLowOutputs
Force all outputs low from HMI
000012
BitGroup1.HMIControls.3
NetFreezeScan
Freeze Scan Control Bit