Specications
The display range of temperature ... 41˚F to 95˚F (5˚C to 35˚C)
The control range of temperature.... 44˚F to 90˚F (7˚C to 32˚C)
Load Rating............................................... 1 amp per terminal, 1.5 amp
maximum all terminals combined
Swing (cycle rate or dierential) ...... Heating is adjustable from 0.2˚ to 2.0˚
Cooling is adjustable from 0.2˚ to 2.0˚
Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz
for hardwire. 500 mA
Operating ambient ............................... 32˚F to +105˚F (0˚C to +41˚C)
Operating humidity .............................. 90% non-condensing maximum
Dimensions of thermostat ................. 4.7” W x 4.3” H x 0.9” D
Frequency Range.................................... 2.4 GHz ISM radio band
WIFI.............................................................. Supporting 802.11 B/G/N Standards
45 46
Specications
Remote Sensor Operation
Option #1 - Indoor / Local Temperature Sensor “ON”:
1. The displayed room temperature will display the average
temperature of the thermostat and all remote sensors.
2. By pressing the far left (Prev Step) button, the average temperature
of just the remote sensor(s) will be displayed briey in the clock eld.
Option #1 - Indoor / Local Temperature Sensor OFF”:
1. The displayed room temperature will only show the average
temperature of the remote sensor(s).
Option #2 - Outdoor:
1. The outdoor temperature will alternate briey with the clock
display.
Option #3 (Floor)
1. By pressing the far left (Prev. Step) button, the temperature of the
oor sensor will be displayed briey in the clock eld.
Remote Sensor Operation Options