Page •38
PF and one for LL. A fourth test result is available: the weight average according to
the formula (4HL+2LL+PF)/7.
The tests results can then be saved.
Before saving, the operator must enter the meter ID, if it was not already entered or
scanned, and must answer up to eight custom questions saved in the MT-1/WT3.
Please note that if Full Test mode had been selected in this example, the test would
have continued, checking each of phases A, B and C, one after the other under the
HL, PF and LL loads.
Note: To speed up the test in Full Test mode, the LL and/or the PF load can be
disabled in the “Settings” tab.
In Full Test mode, once all phases (A, B and C) have been completed and the test for
each phase has begun, you can cancel the test at any time by pressing “STOP TEST.”