6.2 Battery Mode Specifications
Output Waveform
Pure sine wave
Output Voltage Regulation
120 or 230/240Vac± 5%
Output Frequency
50/60Hz ± 0.1%
Nominal DC Voltage
48Vdc
DC voltage range
42.5 ~ 60Vdc(48V)
Low DC warning voltage
42 ~ 55Vdc adjustable
Peak Efficiency
>90%
No Load Power Consumption
28W @48Vdc
THD (Bat. mode)
<3% (Full resistive load)
Load crest factor
3:1 @ rated load
Overload protection
5s@≥125 ~150% load; 60s@110%~125% load
Output short circuit protection
Output breaker/ electronic current limit/ firmware
Surge Capacity
200% * rated power for 5sec
Back feed protection
Yes
Power limitation
Output P
ower
2000VA/1600W
1500VA/1200W
-
40
75
55
1250VA/1000W
80 (120Vac model)
65
Temperature
(°C)
70 (230/240Vac model)