EasyManua.ls Logo

PROLiNK Professional II+ Series - 3-3. Alarm Sound; 3-4. Installation of one UPS

PROLiNK Professional II+ Series
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9
3-3. Alarm Sound
Information
Status buzzer
Mute
Status UPS
Mode Bypass
Sound once every 2 minutes
Yes
Battery mode
Sound once every 4 seconds
Error mode
Continuous sound
COMMEMORATION
Overloaded
Sound twice every second
Not
Low battery
Sound once every second
Battery not connected
Overcharging
Active EPO
Fan malfunction / Overtemperature
Charger failure
Excess 3 times in 30 minutes
Status EPO
Maintenance switch cover opens
Error
Bus start failure
Continuous sound
Yes
Excess buses
Bus less
Unbalanced Bus
Inverter Error
High Inverter Voltage
Low Inverter Voltage
Short circuit inverter output
SCR battery is short connected
Excess temperature
Overloaded
3-4. Installation of one UPS
1.
Turn on the UPS with utility power supply (in AC mode)
Once the power supply is properly connected, set the battery breaker to the "ON" position (this step is only
for Long-Run models). Then set the input breaker at the "ON" position. If using a 30KVA unit, please also
set the bypass breaker at the "ON" position. At this time, the fan is running and the UPS goes into power
on mode for initialization. A few seconds later, the UPS operates in Bypass mode and supplies power to
the load via bypass
Note:
When the UPS is in Bypass mode, the output voltage will generate electricity immediately after you
activate the input brake and Bypass breaker (only available for 30KVA models). In Bypass mode, the load
is not protected by the UPS. To protect your precious device, you should turn on the UPS. See next steps
Press and hold the "ON" button for 0.5 seconds to turn on the UPS and the buzzer will sound once. Press
and hold the "ON" button for approximately 0.5 seconds to turn on the UPS and the buzzer will sound
once.
A few seconds later, the UPS will enter AC mode. If the mains power is abnormal, the UPS will operate in
Battery mode without interruption.
NOTE:
When the UPS runs out of battery, it will automatically turn off in Battery mode. When power is
restored, the UPS will turn back on automatically in AC mode.
1) Press and hold the "ON" button for 1 second to turn on the UPS and the buzzer will beep once.
2) A few seconds later, the UPS will enter AC mode. If the utility power is abnormal, the UPS will operate
in battery mode directly.
Note:
When the UPS is running on battery mode, it will shut down automatically. When utility power is restored,
the UPS will automatically restart in AC mode.

Related product manuals